ControlNet Modular Repeater Medium Distance Fiber Module 7

Publication 9904-IN011A-EN-P - October 2000

5. Remove the protective backplane cap as shown in “Remove the Protective

Caps” on page 8.

6. Once attached to the DIN rail, slide modules to the left to mate with the

repeater adapter or another repeater module.

7. Connect the fiber cable as shown in “Connect the Fiber Cable” on page 11.

ATTENTION

!

Be certain that the adapter and repeater modules are secured
together with DIN rail anchors. Failure to do so may result in
the loss of communications and/ or cause damage to the
modules. The total number of modules that can be attached to
the repeater adapter can not exceed four or the total power
consumption of the modules can not exceed 1.6A @ 5VDC,
whichever comes first.

IMPORTANT

If you exceed the module or power limit, you may cause damage
to the repeater adapter and modules.

IMPORTANT

If this is the right–most module, a DIN rail latch must be used on
the right side of the fiber module.