6 Kinetix 5500 Servo Drives

Rockwell Automation Publication 2198-IN001C-EN-P - January 2014

Mount the Kinetix 5500 Drive

Follow these steps to mount the drive in single-axis configurations.

1. Observe these clearance requirements when mounting a single drive to the panel:

Additional clearance is required for cables and wires connected to the top of the
drive.

Additional clearance left and right of the drive is required when mounted adjacent to
noise sensitive equipment or clean wire ways.

The recommended minimum cabinet depth is 300 mm (11.81 in.).

In multi-axis shared-bus configurations, drives must be spaced by aligning the zero-stack
tab and cutout. For mounting, sizing, and configuring shared-bus configurations, refer to
the Kinetix 5500 Servo Drives User Manual, publication

2198-UM001

.

2. Mount the Kinetix 5500 drive to the cabinet subpanel with M4 (#8-32) steel machine

screws torqued to 2.0 N•m (17.7 lb•in), max.

IMPORTANT

Mount the drive in an upright position as shown. Do not mount the drive on its side.

Clearance right of the

drive is not required.

Clearance left of the

drive is not required.

Kinetix 5500

Servo Drive

40 mm (1.57 in.) clearance below

drive for airflow and installation.

40 mm (1.57 in.) clearance above

drive for airflow and installation.

Zero-stack Tab and

Cutout Aligned

Bus-bar system used in bus-sharing
configurations is not shown for clarity.