About the Remote Keypad

1-3

English

Table 1.2 – Keypad Features

Description

1

The PROGRAM key toggles between display and
program modes. The PROGRAM LED turns on
when the drive is in program mode.

2

In display mode, the ENTER key scrolls through the
display parameters.

In program mode, this key toggles between the
parameter number and parameter value.

3

In display mode, the UP ARROW key increments
the local speed reference.

In program mode, this key increments the parameter
number or parameter value.

4

In display mode, the DOWN ARROW key
decrements the local speed reference.

In program mode, this key decrements the
parameter number or parameter value.

5

The DIRECTION key toggles the drive direction
when keypad control is selected (P-10 = 1) and
reverse is enabled (P-03 = 0).

6

The JOG key issues the jog command to the drive
while pressed when keypad control is selected

(P-10 = 1).

1

The drive will jog at the frequency

selected in P-40 (Internal/Jog Frequency).

1

For drives having software version 3.1 and earlier, the JOG key does not
function. The drive will not respond when the JOG key is pressed.

7

The START key issues start commands to the drive
when keypad control is selected (P-10 = 1).

8

The STOP key issues stop and fault reset
commands to the drive.

9

Display - see section 1.2.

10

Status LEDs - see section 1.3.