Guarded Analog Output Modules (T3480)


1 8

Industrial Control Services

·

Potentiometer adjustment tool.

·

Phillips screwdriver

·

I/O module extender, catalog number T3322.

·

PC running the W

INTERPRET

software, used to force the

analog output channels to the specific values for
calibration.

Calibration Preparation

The module must be calibrated while connected to an I/O
chassis of an operational Regent system.

During calibration, the Guarded analog output module will be
disconnected from the actual controlled field devices.

Appropriate precautions should be taken to ensure that the
disconnection of the control signals does not pose a safety risk
to plant personnel or process equipment.

There are Offset and Gain potentiometers for each analog
output channel. In addition there are three reference voltage
potentiometers and four test points to measure the reference
voltages. These potentiometers are located on a circuit board
inside the module's protective clamshell housing (see Figure
12). During the calibration steps you will remove the printed
circuit board from the housing in order to access these
potentiometers for adjustment.

The potentiometers for each analog output channel are
identified in Table 2. The potentiometers labeled R19, R17
and R22 are used to adjust the reference voltages.

Table 2. Potentiometer Identification.

Channel

Offset

Potentiometer

Gain

Potentiometer

1

R101

R100

2

R201

R200

3

R301

R300

4

R401

R400

5

R501

R500

6

R601

R600

Important!