Specifications – Rockwell Automation T3420AF ICS Regent Analog Input Modules User Manual

Page 36

Advertising
background image

Analog Input Modules (T3420A, AF)


3 6

Industrial Control Services

Specifications

Safetybus Power

1.85 load units

Number of Inputs

Eight differential or 16
single-ended (jumper
selectable)

Inputs Per Group

Eight single-ended or four
differential

Ranges

Voltage:




Current:

(using external 250W resistors)


0.00 to +10.00 volts
-10.00 to +10.00 volts
+1.00 to +5.00 volts
0.00 to +5.00 volts
-5.00 to +5.00 volts

0.00 to +20.00 mA
-40.00 to +40.00 mA
+4.00 to +20.00 mA
0.00 to +20.00 mA
-20.00 to +20.00 mA

External Power

None for module electronics;
however, analog field loop
power is not supplied by the
module

Accuracy and Drift

(Accuracy/Drift)

-10 to +10 volts:

0.00 to +10.00 volts:

-5.00 to +5.00 volts:

0.00 to +5.00 volts:

+1.00 to +5.00 volts:

Note: Initial accuracy (% of span)
represents the initial accuracy @
22ºC to 28ºC calibration
temperature.



0.12%/100 ppm/

°

C

0.08%/55 ppm/

°

C

0.13%/110 ppm/

°

C

0.10%/65 ppm/

°

C

0.10%/70 ppm/

°

C

Advertising