Front panel indicators – Rockwell Automation T3420AF ICS Regent Analog Input Modules User Manual

Page 4

Advertising
background image

Analog Input Modules (T3420A, AF)


4

Industrial Control Services

produces an I/O module error indication at the processor
modules and a module fault indication at the I/O module.

Each type of module has a unique identification code that is
read by the controller. This code lets the controller know
which type of module is installed in each I/O chassis slot and
how to address that module and its points specifically. If a
module is removed, or is replaced with a module of a different
type, the processor modules will indicate an I/O module error.

Loopback logic tests periodically write data to the module and
then read it back to determine whether the module’s I/O bus
interface logic is functioning correctly.

Front Panel Indicators

Figure 3 shows the physical features of the analog input
modules. The front panel of each module contains active and
fault status indicators.

Active and Fault Status Indicators

These green and red LEDs indicate the overall health of the
module. During normal operation the green ACTIVE
indicator flashes at the controller's scan rate. If a module
fault occurs the red FAULT indicator turns on and the green
ACTIVE indicator turns off.