Analog Input Modules (T7420A, AF)


1 8

Industrial Control Services

Programming Fault Tolerant Analog Inputs

To program fault tolerant configurations using triplicated
analog input modules, a midvalue element can be used as
shown in Figure 11.

Figure 11. Programming Fault Tolerant Analog Inputs.

In this illustration, VALUE_A_NAME, VALUE_B_NAME,
and VALUE_C_NAME represent the three analog inputs to
be mid-value selected. ERROR_A_NAME,
ERROR_B_NAME and ERROR_C_NAME are the error bits
for the analog inputs. RESULT_NAME is the result of the
mid-value instruction. The field Limit is the integer value, in
similar units to the Value A, B and C variables, that an
analog input can deviate from the mid-value result before
signaling an error (via the Error A, B or C bits). Once an
error bit is set, it is latched. RESET_NAME is the reset bit
used to reset the latched error bits.

Maintenance

There are no user-replaceable parts inside the module.
Modules must be calibrated for the particular input range
within which they will operate. All modules are calibrated
before being shipped by ICS; however, modules require
calibration whenever:

· the module is configured for a different operating voltage

range (factory configuration is 1 to 5 VDC),

· the module is configured for a different operating mode

(factory configuration is 16 channel, single-ended), or

· once per year after installation, to adjust for drift in the

analog circuitry. Drift rates are listed under
Specifications, below. These drift rates should be used to