Rockwell Automation T7420A_AF ICS Regent+Plus Analog Input Modules 60Hz Rejection and Fast Response User Manual

Page 27

Advertising
background image

Analog Input Modules (T7420A, AF)


P D - 7 0 2 3 M a r - 0 6

27

Out of Range Thresholds

Over-range

-10.00 to +10.00 volts:

0.00 to +10.00 volts:

-5.00 to +5.00 volts:

0.00 to +5.00 volts:

+1.00 to +5.00 volts:

Under-range

-10.00 to +10.00 volts:

0.00 to +10.00 volts:

-5.00 to +5.00 volts:

0.00 to +5.00 volts:

+1.00 to +5.00 volts:

Expressed in volts:


+10.30 min., +10.70 max.
+10.30 min., +10.70 max.
+5.15 min., +5.35 max.
+5.15 min., +5.35 max.
+5.12 min., +5.28 max.

-10.30 min., -10.70 max.
-0.30 min., -0.70 max.
-5.15 min., -5.35 max.
-0.15 min., -0.35 max.
+0.88 min., +0.72 max.

Over Voltage Protection

Powered

AI1-AI16:

AREF 1,2:

Acceptable Duration:

Unpowered

AI1-AI16:

AREF 1,2:

Acceptable Duration:

±60 VDC/85 VAC RMS/±400 VDC

±40 VDC/55 VAC RMS/±60 VDC

Indefinite/Indefinite/1 msec

±45 VDC/45 VAC RMS/±400 VDC

±25 VDC/25 VAC RMS/±45 VDC

Indefinite/Indefinite/1 msec

Frequency Response

(-3 dB/-30 dB/Atten. @ 60 Hz)

Single-Ended

T7420A:

T7420AF:

Differential

T7420A:

T7420AF:




7.23 Hz/229 Hz/18.4 dB
10.6 KHz/335 KHz/0.0 dB

3.62 Hz/114 Hz/24.4 dB
5.31 KHz/168 KHz/0.0 dB

Data Update Rate

Single-ended or 16-

channel mode:

Differential or 8-channel

mode:


3.60 msec on a continuous
repeating basis
1.80 msec on a continuous
repeating basis

Isolation

2500 volts minimum (field
wiring to control logic)

Heat Dissipation

9 Watts, 31 BTUs/hour

Advertising