Analog Input Modules (T7420A, AF)


P D - 7 0 2 3 M a r - 0 6

23

Figure 14. I/O Extender Connections for Differential Analog Input Calibration.

Within each pair of jumper posts, make sure that you connect
the voltage source to the jumper posts nearest the front of the

I/O extender. Do not make any connections to the jumper
posts nearest the I/O chassis backplane — these connect to the
actual field wiring attached to the I/O slot terminals on the I/O
chassis.

Calibration Steps

1. Remove the module to be calibrated from the I/O chassis.

2. Install the I/O extender module into the slot from which

the module was removed.

3. Remove the jumpers (if installed) labeled CH1 through

CH16 from the I/O extender module.

Important!