Monitored Digital Input Modules, Type F (T3411F, T3418F)


P D - 6 0 2 7 M a r - 0 6

21

Line fault status is only reported through the Fault Name
variables. Line faults are not reported as a permanent I/O
module fault and do not turn on the associated system control
relay fault bit for the module. Line faults are not latched. If a
line fault condition returns to normal, the Fault Name
variable status also returns to normal.

Fault Name Description

This 40-character field provides a place to describe the input
point fault name definition. The description is used to help
document your system (it does not affect application program
operation).

Disable Fault LED

Marking the Disable Fault LED check box disables the fault
LED for this input point on the face of the input module.
Marking this box does not stop the module from line
monitoring the input circuit and updating the state of the
Fault Name variable, it only stops the module from displaying
line faults on the face of the input module. Line faults are still
reported to the Regent and are available to the application
program through the fault name variable.

This box can be checked for those input points that do not
have line monitor devices (LMDs) installed, or that are spare
and have no field switches connected. In this configuration
the line fault LED will always be off. If you do not check this
box for input points without LMDs installed or unconnected
spare input points, the line fault LED will always be on.

Programming

Inputs are referenced in the application program through the
tag names defined in the I/O Configuration Editor. When
current flows through the input (field switch closed) the input
is said to be on, or have a value of one. In ladder logic, the on
state would produce power flow in a normally open (N.O.)
contact.

Field wiring open circuit or short circuit conditions are
referenced in the application program using the Fault Name
tag names defined in the I/O configuration Editor. When a
line monitor device is installed across the field switch and the
wiring is healthy, the Fault Name status is on. If there is a

Note: