the input module and performing a voted reset, the fault bit is
turned off, restoring the input configuration to the dual mode.

Programming Triple Fault Tolerant Monitored Inputs

Fault tolerant applications that include triplicated monitored
input modules should use the Voter instruction in ladder
logic. The voter instruction performs two-out-of-three voting
of triplicated inputs, storing the voted result in the defined
shared variable. Refer to the Regent User’s Guide section 5,
Working with Programs and Function Blocks for more details
on using the ladder logic Voter instruction.

Maintenance

No periodic maintenance or calibration is required for the
monitored digital input modules. There are no user
replaceable parts inside these modules.

Safety Considerations

The monitored digital input modules are TÜV certified for
Risk Class 5 safety critical inputs. Safety critical

configurations include dual and triple redundant input
modules and associated application voting methods.

In safety critical input applications using a single sensor, it is
important that the sensor failure modes be predictable and
well understood, so there is little probability of a failed sensor
not responding to a critical process condition. In such a
configuration, it is important that the sensor be tested
regularly, either by dynamic process conditions that are
verified in the Regent, or by manual intervention testing.

Redundant sensors can be used with redundant input
modules to eliminate any single points of failure and extend
fault tolerance to include the sensors.

If energize to trip inputs are used in safety critical
applications, line monitor devices must be installed at the
field switches. The Fault Name variables must be configured
and line fault status must be alarmed to plant operations
personnel.