Step 9: verify the precharge resistor wiring – Rockwell Automation Single Precharge Contactor Replacement Kit for LiquiFlo 2.0 AC Fr 3 Drive Ass'y User Manual

Page 9

Advertising
background image

Instruction Manual D2-8100

9

Step 9: Verify the
Precharge Resistor
Wiring

Verify the precharge resistor wiring by measuring across the open precharge
contactor contacts.

From
Contactor
Terminal

To
Contactor
Terminal

Correct
Meter
Reading

L1

T1

9 - 11 ohms

L2

T2

9 - 11 ohms

L3

T3

9 - 11 ohms