Step 9: verify the precharge resistor wiring – Rockwell Automation Single Precharge Contactor Replacement Kit for LiquiFlo 2.0 AC Fr 3 Drive Ass'y User Manual
Page 9
Advertising
Instruction Manual D2-8100
9
Step 9: Verify the
Precharge Resistor
Wiring
Verify the precharge resistor wiring by measuring across the open precharge
contactor contacts.
From
Contactor
Terminal
To
Contactor
Terminal
Correct
Meter
Reading
L1
T1
9 - 11 ohms
L2
T2
9 - 11 ohms
L3
T3
9 - 11 ohms