Conditioning unit specification, Available conditioning units, Trusted – Rockwell Automation T8840 Trusted Temperature FTA User Manual

Page 12: Temperature fta t8840

Advertising
background image

Trusted

TM

Temperature FTA T8840

Issue 4 Apr 10

PD-T8840

12

3.1.2. Conditioning Unit Specification

The following specification applies to all signal conditioning unit types

.

Operating Voltage Range

15 to 30V dc

Power consumption

2W max

Operating Temperature

-40

o

C to +85

o

C

Common mode Isolation

1500V rms

Continuous field voltage withstand

120V rms

Accuracy

+/- 0.3% span

Output Signal range

+1 to +5V

3.1.3. Available Conditioning Units

Input Types

Range

Model Number (A) Model Number (B)

0 to +10mV

7B30-01-1

SCM7B30-01

0 to +100mV

7B30-02-1

SCM7B30-02

0 to +1V

7B30-03-1

SCM7B30-03

+1 to +5V

7B30-05-1

SCM7B30-04

-10mV to +10mV

7B30-06-1

SCM7B30-05

-100mV to +100mV

7B30-07-1

SCM7B30-06

-1V to +1V

7B30-08-1

SCM7B30-07

0 to 10V

Not available

SCM7B30-08

-5 to +5V

Not available

SCM7B31-01

-10 to +10V

Not available

SCM7B31-02

Isolated Voltage

0 to 5V

Not available

SCM7B31-03

4 to 20mA

7B32-01-1

SCM7B32-01

Isolated Current

0 to 20mA

Not available

SCM7B32-02

-100 to +100

o

C (-148 to +212

o

F)

7B34-01-1

SCM7B34-01

0 to +100

o

C (+32 to +212

o

F)

7B34-02-1

SCM7B34-02

0 to +200

o

C (+32 to +392

o

F)

7B34-03-1

SCM7B34-03

0 to +600

o

C (+32 to +1112

o

F)

7B34-04-1

SCM7B34-04

Isolated RTD

Pt 100ohm

Linearized

-50 to +350

o

C (-58 to +662

o

F)

7B34-05-1

SCM7B34-05

0 to +300

o

C (+32 to +572

o

F)

7B34-N-01-1

SCM7B34N-01

Isolated RTD

Ni 120ohm

Linearized

0 to +200

o

C (+32 to +392

o

F)

7B34-N-02-1

SCM7B34N-02

Isolated 2 wire

Transmitter

(inc loop power)

4 to 20mA

7B35-01-1

SCM7B35-01

Advertising