2. Installation

2.1. Cable Selection

The Trusted

TM

Temperature FTA can connect direct to an Analogue Input Module using either

companion cables TC-211/212 or smart-slot cables TC-511/512. The Output can also be connected to
the Analogue Input module via a VFTA if necessary to be compatible with an existing installation.

Some isolator modules will float their output to 10V on an open circuit field input. This will cause slice
faults on the analogue input module. If the isolator output is connected to the module via a 250R
resistor on a VFTA, the voltage will be pulled down into the module’s operating range. Therefore even
if the isolator output is a voltage signal, it is recommended to connect the input via a VFTA with the
250R VFTA resistor in parallel.

Figure 2 System connectivity using 1-5v output devices

Analogue
module

8431/ 8432

Temperature
FTA

8840

Temperature
FTA

8840

Temperature
FTA

8840

Temperature
FTA

8840

Temperature
FTA

8840

TC-211/212

Typical Configuration using conditioning
Devices with 1-5v output

Up to 8 temperature devices