2. Installation
2.1. Cable Selection
The Trusted
TM
Temperature FTA can connect direct to an Analogue Input Module using either
companion cables TC-211/212 or smart-slot cables TC-511/512. The Output can also be connected to 
the Analogue Input module via a VFTA if necessary to be compatible with an existing installation. 
Some isolator modules will float their output to 10V on an open circuit field input. This will cause slice 
faults on the analogue input module. If the isolator output is connected to the module via a 250R 
resistor on a VFTA, the voltage will be pulled down into the module’s operating range. Therefore even 
if the isolator output is a voltage signal, it is recommended to connect the input via a VFTA with the 
250R VFTA resistor in parallel. 
Figure 2 System connectivity using 1-5v output devices
Analogue 
module 
8431/ 8432
Temperature 
FTA 
8840
Temperature 
FTA 
8840
Temperature 
FTA 
8840
Temperature 
FTA 
8840
Temperature 
FTA 
8840
TC-211/212
Typical Configuration using conditioning 
Devices with 1-5v output 
Up to 8 temperature devices