Figure 3 system connectivity using vfta, Trusted, Temperature fta t8840 – Rockwell Automation T8840 Trusted Temperature FTA User Manual

Page 8

Advertising
background image

Trusted

TM

Temperature FTA T8840

Issue 4 Apr 10

PD-T8840

8

Figure 3 System connectivity using VFTA

For signal conditioning units that provide signals as 4 to 20mA for low to high engineering range, a
conversion is needed because the voltage measured by the module input is not exactly 1 to 5 volts.

EU = ((count/4036.5) – 0.007828) x (HEU – LEU) + LEU

Where:

LEU = Low engineering unit range

HEU = High engineering unit range

Count = Raw value seen by input

EU = Engineering unit value

For signal conditioning units that provide a voltage signal of 1 to 5 volts, no special factors are required:

EU = (count/4096) x (HEU – LEU) + LEU.

VFTA

8842

Temperature
FTA

8840

Temperature
FTA

8840

Temperature
FTA

8840

Temperature
FTA

8840

Temperature
FTA

8840

Typical Configuration using conditioning
Devices with 1 to 5V output Using a VFTA

Up to 8 temperature devices

Analogue
module

8431