Rockwell Automation 20G PowerFlex 750-Series Replacement Board Kits User Manual

Page 11

Advertising
background image

Rockwell Automation Publication RA-IN028C-EN-P - January 2013

PowerFlex 750-Series Board Replacement Kits

11

400/480V Frame 7 Drives – AC and DC Precharge Boards (Continued)

2.6 N•m (23 lb•in)

T20

M4 x 7.0

2.6 N•m (23 lb•in)

M6 x 1.0

5.2 N•m (46 lb•in)

5

PE-A

5.2 N•m (46 lb•in)

T30

4

IMPORTANT: Note the

position of the PE-A jumper

wire before disassembly (AC

Precharge Boards only).

Use the same position when

installing the replacement

board.

Positions are identified in

Step 1 on

page 9

.

Control Cable Position

DC Precharge Boards

600/690V Frame 7 Drives

Control Cable Position

AC Precharge Boards

ATTENTION: Hazard of equipment damage exists if any board connector is not in full contact with its corresponding
socket when power is applied. When installing the replacement board, carefully align and fully seat the pin connector(s),
plug in the control cable, be sure the PE-A jumper wire is properly terminated (AC Precharge Boards only), and install all
fasteners and torque as indicated.