Rockwell Automation 1440-TPR06-00RE XM-360 Process Module User Manual
Page 71

Publication GMSI10-UM006C-EN-P - August 2010
Specifications 63
Signal Conditioning
Accuracy
Low Pass Filter
Resolution
Measurement Units
1% of full scale max
±0.2% of full scale typical
User configurable for the measurement
value and rate of change value from each
channel
0.05% of input range
Deg C PSI
Deg F inHg
CFM mbar
m/s2 Pa
g kPa
gSE mA
RPM ips
Hz mm/s
mm V
um radian
in revolution
mil degree
percent unspecified
Measured Parameters
Measured Value
Rate of Change Per minute
Updated once per second
Delta Time Buffer
Number or Records
Delta Time Interval
Trigger Mode
2048
1 to 3600 seconds
Relay on the XM-441 Expansion Relay
module is activated, or by a trigger event
(for example, DeviceNet command from a
controller or host).
The data collected in the buffer is user
configurable in software.
Alarms
Number
Alarm Parameters
Operators
Hysteresis
12 alarm and danger pairs
Measurement value and rate of change
value from each channel
Greater than
Less than
Inside range
Outside range
User configurable in software
XM-360 Technical Specifications
Product Feature
Specification