MDO32BNS October 2005 – Issue 7

Triguard SC300E

The module uses hardware circuitry and configuration links that enable the system to identify
the module type and configuration mode. The configuration links 1, 2 and 3 are located in the
top right-hand corner of the module (see Figure 1.1).

Link 1 allows the module to be set up for 321 or 320 mode operation. 320 mode means that the
system will continue to function with two out of three serviceable circuits. In 321 mode the
system will continue to function with one out of three serviceable circuits. No link; defaults to

320 mode.

Link 2 (HLV/GTZ) determines whether, in the event of a failure due to 321/320 action, the last
read values are held (HLV) or are set to zero (GTZ). No link; defaults to GTZ mode.

Link 3 is factory set to HW and if changed to ICCB (see Note) or removed the module defaults
to GTZ.

(NOTE: ICCB is a silk screen identifier used on output modules only)

Table 2-1. Link settings versus operation

Link settings (see Notes)

Processor and interface status

Link 1

Link 2

Link 3

3 MPPs & associated
path CI operating

2 MPPs & associated
path CI operating

1 MPP & associated
path CI operating

321

X

X

Normal

Normal

Normal

320

HLV

HW

Normal

Normal

HLV

320

HLV

ICCB

Normal

Normal

GTZ

320

GTZ

X

Normal

Normal

GTZ

320

Missing

X

Normal

Normal

GTZ

Notes:

X = Don’t care or missing link

Link 1 missing = 320 operation

HL = Last valid output held (Output maintained) GTZ = Go To Zero (Output turned off)