Rockwell Automation MDO32BNS 32-Channel Digital Output Module User Manual

Page 4

Advertising
background image

4

MDO32BNS October 2005 – Issue 7

Triguard SC300E

Model

MDO32BNS

Module power
consumption including
field power dissipation in
module

19W @ minimum load

59W @ maximum load

Overall size (mm) Overall
size (inches)

400(9U)H x 397L x 28W

15.75H x 15.63L x 1.1W

Weight

1.8kg

ENVIRONMENTAL SPECIFICATION

The maximum ambient temperature measured at the hottest point within the Triguard system
shall not be greater than 60 degrees centigrade.

Temperature operating:

+5°C to +60°C

Temperature storage:

-25°C to +70°C

Humidity

5% to 95% non-condensing at ambient <40°C

EMC/RFI Immunity

Tested and certified to IEC 1131-Part 2 1994

Vibration/Shock

Tested and certified to IEC 1131-Part 2 1994

Certification:

General Certification: Ref. SC300E Product Guide (ref 008-5209)

TRANSPORT AND HANDLING

The MDO32BNS must be transported and stored in its original packing material which should be
retained for this purpose

Advertising