Line Monitored Input Point dialog, enter names and
values for the configuration fields as described below.

Figure 11. Defining a Monitored Digital Input Point.

Name

Also called the tag name, this is the name used in the
application program to reference the field input switch’s
On/Off state. The name can be up to 12 characters long.

Description

This 40-character field provides a place to describe the input
point definition. The description is used to help document
your system (it does not affect application program operation).

Fault Name

This is the name used in the application program to reference
the input point line fault status. The name can be up to 12
characters long.

During operations the input circuit is monitored for open
circuit and short circuit wiring faults. This bit is normally on
and turns off if either an open circuit or short circuit is
detected.