Specifications – Rockwell Automation T7411F ICS Regent+Plus Monitored Digital input Modules, Field powered (Type F) User Manual

Page 22

Advertising
background image

Monitored Digital Input Modules, Type F (T7411F, T7418F)


2 2

Industrial Control Services

For additional safety considerations, please refer to the Safety
Considerations section of the Regent User’s Guide.

Specifications

Safetybus Power

0.85 load units

Number of Inputs

16, common power

T7411F

T7418F

Field Power

Voltage, min.:

Voltage, max.:

Current:

24 or 48 Vdc

15 Vdc

80 Vdc

450 mA,
maximum

120 Vac/dc

90 Vac/dc

150 Vac/dc

150 mA,
maximum

Turn-On Voltage (default)

> 12 Vdc

> 51 Vdc

Turn-Off Voltage (default)

< 12 Vdc

< 51 Vdc

Input Current

8.0 mA,
maximum

2.0 mA,
maximum

Turn-On Delay

10 msec,
maximum

10 msec,
maximum

Turn-Off Delay

10 msec,
maximum

100 msec,
maximum

Over Voltage Protection

Field Power Terminals:

Input Terminals:

100 Vdc
continuous

100 Vdc
continuous,
160 Vdc for
5 seconds

165 Vac
continuous

230 Vac
continuous,
350 Vac for
5 seconds

Heat Dissipation

8.5 Watts, 29
BTUs/hour

10 Watts, 34
BTUs/hour

Fusing

None, external if required

Isolation

2500 volts minimum (field
wiring to control logic)