Analogue select, Multiple value averaging, Bcd translation – Rockwell Automation T8019 Trusted Process Control Algorithm Software Package User Manual

Page 10: Trusted, Process control algorithms t8019

Advertising
background image

Trusted

TM

Process Control Algorithms T8019

Issue 8 Sep 07

PD-T8019

10

1.3. Analogue Select

R_SEL

PV1

OUT

PV2

SEL

The process variables (PV1 and PV2) and the output (OUT) must all be of type REAL

1

. The select

signal (SEL) is of type BOOLEAN. When SEL is FALSE, PV1 is copied to the output; when SEL is
TRUE, PV2 is copied to the output.

if SEL

Set OUT = PV2

else

Set OUT = PV1

end if

Out is finite if, and only if, the selected PV1 or PV2 is finite.

1.4. Multiple Value Averaging

AVG

N

OUT

PV1

PV2

PV3

PV4

PV5

PV6

PV7

PV8

PV9

PV10

The multiple value averaging calculates the average of between 1 and 10 values (PV1 to PV10). N
specifies the number of values averaged; the first N values are averaged. E.g. if N=3, the average of
PV1, PV2 and PV3 is returned. N is of type INTEGER, PV1 to PV10 and OUT are of type REAL. All
input values must be connected; unused inputs should be tied to either one of the other used inputs or
a constant value.

If the value of N is out of range, i.e. 1>N>10, the average of all ten input values is to be returned and
the “param” error count incremented. Overflow errors occurring whilst calculating the average are to
result in a value of PV1 being returned and the “overflow” error count incremented. If an “underflow”
condition occurs, the function is to set OUT to zero and increment the “underflow” error counter.

1

The standard ISaGRAF SEL function provides the equivalent operation for integer values.

Advertising