Trusted

TM

Process Control Algorithms T8019

Issue 8 Sep 07

PD-T8019

23

Parameters PV, R and H must be finite, i.e. not ±infinities or NaNs. Behaviour is not defined for any
other values. If negative values are specified for R or H, their ABS value will be used and the “param”
error counter will be incremented.

The function must record the sample time for the previous input value and calculate the rate of input
value change for the actual elapsed period.

In an overflow condition occurs, the function is to set Q

UP

to PV>0, Q

DOWN

to PV<0 and increment the

“overflow” error counter. In an underflow condition occurs, the function is to set Q

UP

and Q

DOWN

to

FALSE and increment the “underflow” error counter.