Figure 3 sample application program, Trusted, Process control algorithms t8019 – Rockwell Automation T8019 Trusted Process Control Algorithm Software Package User Manual

Page 21

Advertising
background image

Trusted

TM

Process Control Algorithms T8019

Issue 8 Sep 07

PD-T8019

21

Example:

T_AVG

OUT

PV

250ms

20ms

T (ms)

350

390

432

475

521

565

607

650

690

732

777

821

PV

23.5 15.46

10.01

56.03

58.61

90.17

85.68 84.56

18.09

95.94

75.66

49.38

Ts (ms)

46

40

42

43

46

44

42

43

40

42

45

44

% of Tp

103.2 102.4

101.6

102.8

102.8

104.4

102.8 104.0

103.2

102.8

102.4

102.4

OUT

23.50 22.87

21.09

22.71

28.76

37.26

48.00 58.53

64.87

68.91

73.96

71.92

Table 3 Example Time Average

The example assumes that PV has been static at 23.5 for greater than 250 ms before the first sample
shown. The Ts row shows the actual interval between samples. The % of Tp row shows the figure
used for the overall output adjustment; e.g., the actual period between the 521ms and 777ms iterations
is 256ms, i.e. 102.4% of Tp.