Powerflex 700l, Table 32, 600, Table 33, 690 – Rockwell Automation 1336T Wiring and Grounding Guide, (PWM) AC Drives User Manual
Page 100

100
Rockwell Automation Publication DRIVES-IN001M-EN-P - March 2014
Appendix A Motor Cable Length Restrictions Tables
Table 32 - PowerFlex 700H Drives, 600V Shielded/Unshielded Cable – Meters (Feet)
Table 33 - PowerFlex 700H Drives, 690V Shielded/Unshielded Cable – Meters (Feet)
PowerFlex 700L
This section lists motor cable length restrictions, reactors, and available options
for PowerFlex 700L drives.
Drive
No Solution
Reactor Only
Reactor and Damping Resistor
or 1321-RWR
Reactor/RWR
Resistor
Available Options
Frame Hp
kHz 1488V
1850V
1488V
1850V
1488V
1850V
Cat. No.
Ohms
Watts
TF
A1
TF
B
2
RW
R2
RW
C
9
150
2
24.4 (80)
45.7 (150)
61.0 (200)
91.4 (300)
198.1 (650)
365.8 (1200)
1321-RWR200-EP
●
200
2
24.4 (80)
45.7 (150)
61.0 (200)
91.4 (300)
198.1 (600)
365.8 (1200)
1321-RWR250-EP
●
10
250
2
24.4 (80)
45.7 (150)
61.0 (200)
91.4 (300)
167.6 (550)
365.8 (1200)
1321-3RB250-B
50
315
●
350
2
24.4 (80)
45.7 (150)
61.0 (200)
91.4 (300)
167.6 (550)
365.8 (1200)
1321-3RB350-B
20
585
(3)
(3) Resistor specification is based on two parallel cables per phase.
●
400
2
24.4 (80)
45.7 (150)
61.0 (200)
91.4 (300)
167.6 (550)
365.8 (1200)
1321-3RB400-B
20
585
●
450
2
24.4 (80)
45.7 (150)
61.0 (200)
91.4 (300)
167.6 (550)
365.8 (1200)
1321-3R500-B
20
●
11
500
2
24.4 (80)
45.7 (150)
61.0 (200)
91.4 (300)
167.6 (550)
365.8 (1200)
1321-3R500-B
20
●
600
2
24.4 (80)
45.7 (150)
61.0 (200)
91.4 (300)
152.4 (500)
365.8 (1200)
1321-3R600-B
20
●
12
(1)
(1) Frame 12 drives have dual inverters and require two output reactors. The resistor ratings are per phase values for each reactor.
700
2
24.4 (80)
45.7 (150)
61.0 (200)
91.4 (300)
152.4 (500)
365.8 (1200)
2 x 1321-3RB320-B
40
●
800
2
24.4 (80)
45.7 (150)
61.0 (200)
91.4 (300)
152.4 (500)
365.8 (1200)
2 x 1321-3RB400-C
40
480
(4)
(4) Resistor specification is based on three parallel cables per phase.
●
900
2
24.4 (80)
45.7 (150)
61.0 (200)
91.4 (300)
152.4 (500)
365.8 (1200)
2 x 1321-3R400-B
40
480
13
(2)
(2) Frame 13 drives require two output reactors to match drive amp rating. The resistor ratings are per phase values for each reactor.
1000
2
24.4 (80)
45.7 (150)
61.0 (200)
91.4 (300)
152.4 (500)
365.8 (1200)
2 x 1321-3R500-C
20
480
1100
2
24.4 (80)
45.7 (150)
61.0 (200)
91.4 (300)
137.2 (450)
365.8 (1200)
2 x 1321-3R500-B
20
720
(5)
(5) Resistor specification is based on four parallel cables per phase.
1300
2
24.4 (80)
45.7 (150)
61.0 (200)
91.4 (300)
137.2 (450)
365.8 (1200)
2 x 1321-3R600-B
20
720
Drive
No Solution
Reactor Only
Reactor and Damping Resistor
Reactor
Resistor
Available Options
Frame kW
kHz 1850V
2000V
1850V
2000V
1850V
2000V
Cat. No.
Ohms
Watts
TF
A1
TF
B
2
RW
R2
RW
C
9
160
2
7.6 (25)
30.5 (100)
7.6 (25)
30.5 (100)
121.9 (400)
137.2 (450)
1321-3RB250-C
50
480
200
2
7.6 (25)
30.5 (100)
7.6 (25)
30.5 (100)
121.9 (400)
137.2 (450)
1321-3RB250-C
50
480
10
250
2
7.6 (25)
30.5 (100)
7.6 (25)
30.5 (100)
121.9 (400)
137.2 (450)
1321-3RB400-C
50
480
315
2
7.6 (25)
30.5 (100)
7.6 (25)
30.5 (100)
121.9 (400)
152.4 (500)
1321-3RB400-C
20
960
(3)
(3) Resistor specification is based on two parallel cables per phase.
355
2
7.6 (25)
30.5 (100)
7.6 (25)
30.5 (100)
121.9 (400)
152.4 (500)
1321-3R500-C
20
400
2
7.6 (25)
30.5 (100)
7.6 (25)
30.5 (100)
121.9 (400)
152.4 (500)
1321-3R500-C
20
11
450
2
7.6 (25)
30.5 (100)
7.6 (25)
30.5 (100)
121.9 (400)
152.4 (500)
1321-3R750-C
20
500
2
7.6 (25)
30.5 (100)
7.6 (25)
30.5 (100)
121.9 (400)
152.4 (500)
1321-3R750-C
20
560
2
7.6 (25)
30.5 (100)
7.6 (25)
30.5 (100)
121.9 (400)
152.4 (500)
1321-3R850-C
20
12
(1)
(1) Frame 12 drives have dual inverters and require two output reactors. The resistor ratings are per phase values for each reactor.
630
2
7.6 (25)
30.5 (100)
7.6 (25)
30.5 (100)
121.9 (400)
152.4 (500)
2 x1321-3R600-C
40
480
(4)
(4) Resistor specification is based on three parallel cables per phase.
710
2
7.6 (25)
30.5 (100)
7.6 (25)
30.5 (100)
121.9 (400)
152.4 (500)
2 x1321-3R600-C
40
645
(4)
800
2
7.6 (25)
30.5 (100)
7.6 (25)
30.5 (100)
121.9 (400)
152.4 (500)
2 x1321-3R750-C
40
645
(4)
13
900
2
7.6 (25)
30.5 (100)
7.6 (25)
30.5 (100)
121.9 (400)
152.4 (500)
2 x1321-3R600-C
40
645
(4)
1000
(2)
(2) Some Frame 13 drives require two output reactors to match drive amp rating. The resistor ratings are per phase values for each reactor.
2
7.6 (25)
30.5 (100)
7.6 (25)
30.5 (100)
121.9 (400)
152.4 (500)
2 x1321-3R600-C
20
840
(5)
(5) Resistor specification is based on four parallel cables per phase.
1100
2
7.6 (25)
30.5 (100)
7.6 (25)
30.5 (100)
121.9 (400)
152.4 (500)
2 x1321-3R750-C
20
- 1336E Wiring and Grounding Guide, (PWM) AC Drives 1336F Wiring and Grounding Guide, (PWM) AC Drives 1336S Wiring and Grounding Guide, (PWM) AC Drives 1336VT Wiring and Grounding Guide, (PWM) AC Drives 1336 Wiring and Grounding Guide, (PWM) AC Drives 1305 Wiring and Grounding Guide, (PWM) AC Drives 25B Wiring and Grounding Guide, (PWM) AC Drives 20N Wiring and Grounding Guide, (PWM) AC Drives 20M Wiring and Grounding Guide, (PWM) AC Drives 22C Wiring and Grounding Guide, (PWM) AC Drives 22B Wiring and Grounding Guide, (PWM) AC Drives 22A Wiring and Grounding Guide, (PWM) AC Drives 20D Wiring and Grounding Guide, (PWM) AC Drives 20C Wiring and Grounding Guide, (PWM) AC Drives 20B Wiring and Grounding Guide, (PWM) AC Drives 20A Wiring and Grounding Guide, (PWM) AC Drives 1336R Wiring and Grounding Guide, (PWM) AC Drives