Rockwell Automation Publication DRIVES-IN001M-EN-P - March 2014

37

Power Distribution Chapter 2

PowerFlex
700/700S

For
PowerFlex
700S,
replace 20B
with 20D.

20BD1P1

480

0.37 (0.5)

250

3R2-B

20

2

20BD2P1

480

0.75 (1)

250

3R2-B

20

2

20BD3P4

480

1.5 (2)

500

3R4-B

6.5

4

20BD5P0

480

2.2 (3)

500

3R4-B

6.5

4

20BD8P0

480

4.0 (5)

500

3R8-B

3

8

20BD011

480

5.5 (7.5)

750

3R12-B

2.5

12

20BD014

480

7.5 (10)

750

3R18-B

1.5

18

20BD022

480

11 (15)

750

3R25-B

1.2

25

20BD027

480

15 (20)

750

3R35-B

0.8

35

20BD034

480

18.5 (25)

1000

3R35-B

0.8

35

20BD040

480

22 (30)

1000

3R45-B

0.7

45

20BD052

480

30 (40)

1000

3R55-B

0.5

55

20BD065

480

37 (50)

1000

3R80-B

0.4

80

20BD077

480

45 (60)

1000

3R80-B

0.4

80

20BD096

480

55 (75)

1000

3R100-B

0.3

100

20BD125

480

75 (100)

1000

3R130-B

0.2

130

20BD140

480

75 (100)

1000

3R160-B

0.15

160

20BD156

480

90 (125)

1500

3R160-B

0.15

160

20BD180

480

110 (150)

1500

3R200-B

0.11

200

20BE0P9

600

0.37 (0.5)

250

3R2-B

20

2

20BE1P7

600

0.75 (1)

250

3R2-B

20

2

20BE2P7

600

1.5 (2)

500

3R4-B

6.5

4

20BE3P9

600

2.2 (3)

500

3R4-B

6.5

4

20BE6P1

600

4.0 (5)

500

3R8-B

3

8

20BE9P0

600

5.5 (7.5)

750

3R8-B

3

8

20BE011

600

7.5 (10)

750

3R12-B

2.5

12

20BE017

600

11 (15)

750

3R25-B

1.2

25

20BE022

600

15 (20)

750

3R25-B

1.2

25

20BE027

600

18.5 (25)

1000

3R35-B

0.8

35

20BE032

600

22 (30)

1000

3R35-B

0.8

35

20BE041

600

30 (40)

1000

3R45-B

0.7

45

20BE052

600

37 (50)

1000

3R55-B

0.5

55

20BE062

600

45 (60)

1000

3R80-B

0.4

80

20BE077

600

55 (75)

1000

3R80-B

0.4

80

20BE099

600

75 (100)

1200

3R100-B

0.3

100

20BE125

600

90 (125)

1400

3R130-B

0.2

130

20BE144

600

110 (150)

1500

3R160-B

0.15

160

(1) Maximum suggested KVA supply without consideration for additional inductance

Table 11 - AC Line Impedance Recommendations for PowerFlex 700/700S Drives (Continued)

Drive

Drive Catalog
Number

Volts

kW (Hp)

Max Supply
KVA

(1)

3% Line Reactor
Open Style 1321-

Reactor Inductance
(mH)

Reactor Current
Rating (amps)

Advertising