Table 45, 690 – Rockwell Automation 1336T Wiring and Grounding Guide, (PWM) AC Drives User Manual
Page 108

108
Rockwell Automation Publication DRIVES-IN001M-EN-P - March 2014
Appendix A Motor Cable Length Restrictions Tables
Table 45 - PowerFlex 700S Drives, 690V Shielded/Unshielded Cable – Meters (Feet)
Drive
No Solution
Reactor Only
Reactor and Damping
Resistor
Reactor
Resistor
Available Options
Frame kW
kHz 1850V
2000V
1850V
2000V
1850V
2000V
Cat. No.
Ohms
Watts
TF
A1
TF
B
2
RW
R2
RW
C
5
45
2/4
24.4 (80)
45.7 (150)
61.0 (200)
106.7 (350)
365.8 (1200)
365.8 (1200)
1321-3R80-C
50
375/750
55
2/4
24.4 (80)
45.7 (150)
61.0 (200)
106.7 (350)
365.8 (1200)
365.8 (1200)
1321-3R80-C
50
375/750
75
2/4
24.4 (80)
45.7 (150)
61.0 (200)
106.7 (350)
365.8 (1200)
365.8 (1200)
1321-3R100-C
50
375/750
90
2/4
24.4 (80)
45.7 (150)
61.0 (200)
106.7 (350)
243.8 (800)
274.3 (900)
1321-3R130-C
50
375/750
6
110
2/4
24.4 (80)
45.7 (150)
76.2 (250)
121.9 (400)
243.8 (800)
274.3 (900)
1321-3R160-C
50
375/750
132
2/4
24.4 (80)
45.7 (150)
76.2 (250)
121.9 (400)
243.8 (800)
274.3 (900)
1321-3R200-C
50
375/750
9
160
2
24.4 (80)
45.7 (150)
91.4 (300)
121.9 (400)
182.9 (600)
243.8 (800)
1321-3RB250-C
50
480
200
2
24.4 (80)
45.7 (150)
91.4 (300)
121.9 (400)
182.9 (600)
243.8 (800)
1321-3RB250-C
50
480
10
250
2
24.4 (80)
45.7 (150)
91.4 (300)
121.9 (400)
182.9 (600)
243.8 (800)
1321-3RB400-C
50
480
315
2
24.4 (80)
45.7 (150)
91.4 (300)
121.9 (400)
182.9 (600)
243.8 (800)
1321-3RB400-C
20
960
(3)
(3) Resistor specification is based on two parallel cables per phase.
355
2
24.4 (80)
45.7 (150)
91.4 (300)
121.9 (400)
182.9 (600)
243.8 (800)
1321-3R500-C
20
960
400
2
24.4 (80)
45.7 (150)
91.4 (300)
121.9 (400)
182.9 (600)
243.8 (800)
1321-3R500-C
20
960
11
450
2
24.4 (80)
45.7 (150)
91.4 (300)
121.9 (400)
182.9 (600)
243.8 (800)
1321-3R750-C
20
960
500
2
24.4 (80)
45.7 (150)
91.4 (300)
121.9 (400)
182.9 (600)
243.8 (800)
1321-3R750-C
20
960
560
2
24.4 (80)
45.7 (150)
76.2 (250)
121.9 (400)
182.9 (600)
243.8 (800)
1321-3R850-C
20
960
12
(1)
(1) Frame 12 drives have dual inverters and require two output reactors. The resistor ratings are per phase values for each reactor.
630
2
24.4 (80)
45.7 (150)
76.2 (250)
121.9 (400)
182.9 (600)
243.8 (800)
2 x 1321-3R600-C
40
480
(4)
(4) Resistor specification is based on three parallel cables per phase.
710
2
24.4 (80)
45.7 (150)
76.2 (250)
121.9 (400)
182.9 (600)
243.8 (800)
2 x 1321-3R600-C
40
645
(4)
800
2
24.4 (80)
45.7 (150)
76.2 (250)
121.9 (400)
182.9 (600)
243.8 (800)
2 x 1321-3R750-C
40
645
(4)
13
900
2
24.4 (80)
45.7 (150)
76.2 (250)
121.9 (400)
182.9 (600)
243.8 (800)
2 x 1321-3R600-C
40
645
(4)
1000
(2)
(2) Some Frame 13 drives require two output reactors to match drive amp rating. The resistor ratings are per phase values for each reactor.
2
24.4 (80)
45.7 (150)
61.0 (200)
91.4 (300)
182.9 (600)
243.8 (800)
2 x 1321-3R600-C
20
840
(5)
(5) Resistor specification is based on four parallel cables per phase.
1100
2
24.4 (80)
45.7 (150)
61.0 (200)
91.4 (300)
182.9 (600)
243.8 (800)
2 x 1321-3R750-C
20
840
- 1336E Wiring and Grounding Guide, (PWM) AC Drives 1336F Wiring and Grounding Guide, (PWM) AC Drives 1336S Wiring and Grounding Guide, (PWM) AC Drives 1336VT Wiring and Grounding Guide, (PWM) AC Drives 1336 Wiring and Grounding Guide, (PWM) AC Drives 1305 Wiring and Grounding Guide, (PWM) AC Drives 25B Wiring and Grounding Guide, (PWM) AC Drives 20N Wiring and Grounding Guide, (PWM) AC Drives 20M Wiring and Grounding Guide, (PWM) AC Drives 22C Wiring and Grounding Guide, (PWM) AC Drives 22B Wiring and Grounding Guide, (PWM) AC Drives 22A Wiring and Grounding Guide, (PWM) AC Drives 20D Wiring and Grounding Guide, (PWM) AC Drives 20C Wiring and Grounding Guide, (PWM) AC Drives 20B Wiring and Grounding Guide, (PWM) AC Drives 20A Wiring and Grounding Guide, (PWM) AC Drives 1336R Wiring and Grounding Guide, (PWM) AC Drives