Rockwell Automation DeviceNet System Quick Reference User Manual

Page 10

Advertising
background image

DeviceNet System Quick Reference

DNET-QR001A-EN-E – March 2009

10

6. If AutoScan is selected and set to Disable, press the Up Arrow

to change to Enable.

7. Press SEL

to select Mapping and press 3, 2, and then Enter

.

8. Press SEL

and then Enter

to save your changes.

AutoScan begins and the Active Nodes value increments. When the value reaches a node count
of 6, AutoScan is finished and found all 6 nodes on the network.

9. Select AutoScan and press the Up Arrow

to change to Disable.

10. Press SEL

twice and then press Enter

to save your changes.

AutoScan is disabled in the scanner.

11. Press ESC

three times to return to the Network Who dialog box on the 193-DNCT terminal.

12. Turn the key on the front of the 1756-L63 controller (in slot 2) completely counter-clockwise.

This puts the ControlLogix controller back into Run mode, which will also put the scanner module
into Run mode, provided that the scanner run bit is set by the logic or data table.

View the I/O Mapping Information

Once all of the devices have been added to the scanlist via AutoScan, you can check the I/O data
mapping that was generated by AutoScan. The 193-DNCT terminal can view the input and output data
sizes along with the input and output data mapping assignments for each device.

1. In the Network Who dialog box, press the Up Arrow

to navigate to and select the first line

(0 – 1756-DNB DeviceNet Scanner).

2. Press Enter

to go to its configuration dialog box.

3. Press the Down Arrow

to navigate to and select Scanner and press Enter

.

4. Press the Down Arrow

to navigate to and select ScanList and press Enter

.

This ScanList dialog box appears.

ScanList

0 -- DeviceNet Scanner

2 -- 100-DNY42
5 -- E1 Plus
6 -- Parker Valve
7 -- E1 Plus
8 – 100-DNY42
62 – This DeviceNet HIM

Advertising