DeviceNet System Quick Reference
DNET-QR001A-EN-E – March 2009
8
Follow these steps to set the communication rate to 125 Kbps.
1. Press SEL
to advance to BaudRate.
2. Select BaudRate and press the Up Arrow
to choose 125 Kbps.
3. Press ESC
to exit Setup.
Change Node Number 63 to Node Number 1
No entry exists for node 1 in the Network Who dialog box because the device is currently at node 63.
Follow these steps to change to node number from 63 to 1.
1. On the 193-DNCT keypad, press the Down Arrow
to scroll through the list and select ‘63 – No
Product Name’.
2. Press Enter
to advance to the configuration dialog box.
3. Press the Down Arrow
to select Tools.
4. Press Enter
.
A dialog box appears with NodeComm selected.
5. Press Enter
again.
The Node Commissioning dialog box appears with BaudRate selected.
6. Press SEL
to advance to Address and select it.
7. To change the Address, press 1 and then Enter
.
An Apply Changes dialog box appears.
Tip: You can use the Up Arrow
and Down Arrow
to scroll through the node numbers.
8. Press SEL
and then Enter
to complete the node commissioning.
After approximately 2 seconds the 193-DNCT terminal re-initializes. In another 10 seconds, the
terminal again displays the Network Who dialog box with node 1 now visible.
Node Commissioning
--------------------------------------
BaudRate: 125K
Address: 63