Line Monitoring Thresholds
The module determines the contact state and line fault status by comparing the input voltage level to 
four user programmed thresholds and two fixed (minimum and maximum) thresholds. Hysteresis is 
provided on the thresholds by up-scale and downscale values, corresponding to the thresholds for 
increasing and decreasing values respectively. 
Typical 
voltage 
threshold 
values 
Input 
Channel 
State 
 
Line Fault 
Status 
Over-range
6
1
Tmax
6.0
High-High
5
0
T8
2.28
4 or 51
T7
2.24
High
4
0
T6
1.82
3 or 4
0
T5
1.79
Normal
3
0
T4
1.52
2 or 3
T3
1.47
Low
2
0
T2
1.12
1 or 2
T1
1.11
Low-Low
1
1
Tmin
0
Under-range
0
1
Table 1 Example Threshold data
1
The channel state value returned is dependent on the previous state value. If the input level is
increasing then the lower state value will be returned. If the input level is decreasing the higher state 
value will be returned .Default threshold values used for non line monitored inputs are as follows (in 
raw units) Default = 448,576,1344,1472,2240,2368,3520,3648,5120