3.2.4. Rack 4: THRSHOUT
This board allows the current thresholds for an analogue input channel to be read or written by the 
application. The application can write new thresholds in the THRSHOUT board for a particular channel, 
and it can read the current thresholds from the THRSHIN board, under control of a channel in the 
THRSHOUT board. 
Channel
Description
1
Write the threshold data for a particular 
input channel on channels 3 to 11 to the 
module. The data is written on a rising 
edge 0 to 1. 
2
Read the threshold data for a particular 
channel from the module to the THRSHIN 
board. The data is read on a rising edge 0 
to 1. 
3
Channel number to write/read threshold 
data. Range 1 to 60. 
4
States 2 > 1 falling threshold
5
States 1 > 2 rising threshold
6
States 3 > 2 falling threshold
7
States 2 > 3 rising threshold
8
States 4 > 3 falling threshold
9
States 3 > 4 rising threshold
10
States 5 > 4 falling threshold
11
States 4 > 5 rising threshold
Table 10 Rack 4: THRSHOUT descriptions