Bit Number 
7
6
5
4
3
2
1
0
Standby Module
Active Module
Ejector 
open 
FCR C 
Healthy 
FCR B 
Healthy 
FCR A 
Healthy 
Ejectors 
open 
FCR C 
Healthy 
FCR B 
Healthy 
FCR A 
Healthy 
Table 16 Rack 8: FCR bit descriptions
The ‘Primary Module is active’ channel is set to non-zero if the primary module is the current active 
module, i.e. the active module is in the chassis and slot numbers defined within the OEM parameters. 
The ‘Active Module is simulated’ channel is set to non-zero if the active module is being simulated, this 
will only be set if the module is not present and the simulation enable has been set within the module’s 
configuration in the system.ini file. 
3.3.
Sequence of Events Configuration
Each Boolean Input Variable can be configured for automatic Sequence of Events (SOE) logging. This 
applies to the Input Status and Line Fault Status variables. A Boolean variable is configured for SOE 
during the variable definition in the Data Dictionary Editor. To select SOE, press the Extended Button 
in the Boolean Variable Definition Dialog Box to open the Extended Definition Dialog. Then check the 
box for Sequence of Events to enable the variable for automatic SOE logging. 
During operation, the input module automatically reports time-stamped change of state information for 
the input data. The TMR Processor automatically logs change of state for configured SOE variables 
into the system SOE Log. The SOE Log can be monitored and retrieved using the SOE and Process 
Historian Package running on the EWS. This software package is described in PD-8013. 
3.4.
SYSTEM.INI File Configuration
There are many operating characteristics of the input module that can be customised for a particular 
application. The System Configuration Manager is a tool that allows the user to configure the specific 
operating characteristics for each module. Descriptions of the items that may be configured for the 
Trusted
TM
24V dc Analogue Input Module T8432 are contained in PD-8082B.
Certain characteristics apply to the entire module and are considered Module Configurable Items. 
Other characteristics apply to individual input channels and are considered Channel Configurable 
Items. There are specific default settings for each of the configurable items. If the default settings are 
appropriate for a given application, then customization of the module definition in the System 
Configuration Manager is not required.