Specifications – Rockwell Automation T7491 ICS Regent+Plus Mixed I/O Modules User Manual

Page 18

Advertising
background image

Multiplexed I/O Module (T7491)


1 8

Industrial Control Services

Specifications

Safetybus Power

1.0 load units

Mux I/O Capacity

Maximum 12 MIU
processors supporting a total
of 8 Mux Input Units (512
points) and 4 Mux Output
Units (256 points).

Compatible MIU Equipment

MIU 3201: Multiplexed I/O
Processor Unit,
MIU 3202: Multiplexed
Input Unit, 64-channel,
MIU 3204: Multiplexed
Output Unit, 64-channel

Port Type

Two isolated RS-422 ports

Protocol

Subset of ICS2000 I/O
communications protocol

Operating Modes

Two independent single
communications links, or
Dual voted communications
links (2oo2)

Baud Rate

9,600 or 19,200 baud

Maximum Distance

approximately 4000 feet
(1220 m) @ 19,200 baud,
8000 feet (2440 m) @ 9,600
baud

Isolation

1,000 volts minimum (serial
port to serial port)
1,000 volts minimum (serial
port to logic)

Heat Dissipation

4.5 Watts, 15 BTUs/hour

Operating Temperature

0

°

to 60

°

C

(32

°

to 140

°

F)

Storage Temperature

-40

°

to 85

°

C

(-40

°

to 185

°

F)