1.5. Line Monitoring Thresholds
The module determines the contact state and line fault status by comparing the input voltage level to 
four user programmed thresholds and two fixed (minimum and maximum) thresholds. A “Contact 
Indeterminate” region is defined between the contact Closed and Open states to account for marginal 
faults in the external wiring or in the IFIU. Hysteresis is provided on the thresholds by up-scale and 
downscale values, corresponding to the thresholds for increasing and decreasing values respectively. 
 
Typical voltage 
threshold 
values 
Input 
Channel 
State 
 
DI 
Status 
 
Line Fault 
Status 
Over-range
6
0
1
Tmax
32.0
Short Circuit
5
T8
20.0
4 or 51
0/1
0/1
T7
19.5
Contact Closed
4
‘1’
0
T6
16.0
3 or 4
0/1
0/1
T5
15.5
Contact Indeterminate
3
0
1
T4
8.5
2 or 3
0
T3
8.0
Contact Open
2
T2
4.5
1 or 2
0/1
T1
4.0
Open Circuit
1
1
Tmin
0.0
Under-range
0
Table 1 Example Threshold data (24Vdc)
When a module is inserted into the standby slot in a line-monitored application, then the field 
terminations for all the input channels are paralleled, resulting in a drop in the input voltages for the 
active module. 
The threshold values are recalculated and configured so that this does not result in the inadvertent 
reporting of the Contact-Open or Contact-Indeterminate states. 
 
1
The channel state value returned is dependent on the previous state value. If the input level is
increasing then the lower state value will be returned. If the input level is decreasing the higher state 
value will be returned.