PD-T8402

19

The IEC1131 TOOLSET conversion tables may be used to convert the input value to engineering
units, in this case voltage. The full-scale range for this number format is decimal ±64, corresponding
to physical range –32768 to +32767. Other units may be chosen depending on the numeric resolution
and span of the desired result.
When the TMR Processor detects a 1-oo-2D channel fault or discrepancy, or if the input module is
simulated, the input voltage numeric value is reported as –2048.

3.2.4. Rack 4: SPARE

This rack is reserved for future used and is included to promote consistency with other Trusted

TM

I/O

modules.

3.2.5. Rack 5: LINE_FLT

Channel

Description

1

Field input channel 1 line fault

2

Field input channel 2 line fault

60

Field input channel 60 line fault

Table 10 Rack 5: LINE_FLT

The line fault input is reported as true (logic ‘1’) for a line fault condition (open circuit, indeterminate, or
short circuit condition). The logic state is the majority voted value.
When the TMR Processor detects a 1-oo-2D channel fault or discrepancy, or if the input module is
simulated, the line fault input is set to True.

3.2.6. Rack 6: DISCREP

Channel

Description

1

Discrepancy status inputs 1 to 16 (input 1 is LSB, bit 0)

2

Discrepancy status inputs 17 to 32 (input 17 is LSB, bit 0)

3

Discrepancy status inputs 33 to 48 (input 33 is LSB, bit 0)

4

Discrepancy status inputs 49 to 60 (input 49 is LSB, bit 0, bits 12 – 15 are set to
zero)

Table 11 Rack 6: DISCREP bit descriptions

Each of the integers reports the discrepancy status of 16 input channels. The corresponding bit within
the integer is set to ‘1’ when a discrepancy condition is detected on that input channel’s input state
(rack 2). For example, if slice B of the input module reports the state of channel 4 as state 5, while
slice A reports channel 4 as state 2, then slice B has a channel discrepancy for channel 4. In this
case, bit 3 of channel 1 on the Discrepancy board would be set to ‘1’.