7. Specifications
Voltage Range
22 to 28V dc
Input Current
60A max
MCB Outputs
4-off, 2x24V and 2x0V at 20A
1 off, 1x24V and 1x0V at 3A
Common Alarm Output
1-off N/O volt-free contact –
closed in the healthy state
Connectors
LU10.16 screw clamp terminal
FCI Qikmate SMS series
connector
Conductor Clamping Range (LU10.16)
0.5 to 16mm
2
Max Switching Voltage
60V dc or 125V ac
Operating Temperature
-5°C to 60°C (23°F to 140°F)
Non-operating Temperature
-25°C to 70ºC (-13°F to 158°F)
Operating Humidity
5 to 95% RH
Environmental Specifications
Refer to Document 552517
Dimensions
Height
Width
Depth
108mm (4.2ins)
240mm (9.4ins)
109mm (4.3ins)
Weight
823gms (1.8lbs.)