Trusted

TM

Power Distribution Unit MCB 24Vdc T8292

Issue 8 Nov 08

7

1. Description

The schematic diagram for the Trusted

TM

Power Distribution Unit MCB 24V dc is shown in Figure 2

below.

Figure 2 Trusted

TM

Power Distribution Unit MCB 24V dc Schematic Diagram

Only one 20A output TB1 is shown for clarity. Note that both 24V supplies on TB1 are connected to
feeder 24V-1. TB2 is also wired to 24V-1. TB3 and TB-4 are powered from 24V-2. This means that if a
separated dual redundant supply is required, each output must be wired to one supply on 24V-1 and
one supply on 24V-2. Figure 3 shows a simplified diagram of the connections.

TB1

0V

0V

1

2