Status indicators, Figure 3 single line power diagram, Trusted – Rockwell Automation T8xxx Trusted Power Distribution Unit MCB 24Vdc User Manual

Page 8

Advertising
background image

Trusted

TM

Power Distribution Unit MCB 24Vdc T8292

Issue 8 Nov 08

8

Figure 3 Single line power diagram

Power fed to the Trusted

TM

Power Distribution Unit MCB 24V is sub-distributed via the dual MCBs

either as an N+1 or 100% redundant configuration, via the fitting (for N+1) or removal of the board
mounted link, LK-N+1.

The standard factory-fitted configuration is N+1.

Each MCB is monitored for open circuit condition and provides a local on-board LED indication of
individual ‘trip’ status (red LED displayed for tripped).

A volt-free relay contact provides the common alarm output signal (contact open for tripped) for
connection to external alarm monitoring circuits.

For modules up to issue 5 the maximum difference between supply feeds must not exceed 1V.

2. Status Indicators

2-off green LEDs

On to indicate that each power supply feeder is healthy.

10-off red LED

On to indicate that the adjacent MCB has tripped.

24V-1

24V-2

TB1

TB2

TB3

TB4