Rockwell Automation Liqui-Flo AC Power Modules User Manual
Page 92

A-2
LiquiFlo AC Power Modules, Hardware Reference Version 6.4
Table A.2 – Environmental Conditions
Condition
Specification
Operating Temperature (inside an enclosure)
0
°C to 55°C
*
(32°F to 131°F)
*
User-supplied cabinet air cooling system must provide adequate heat dissipation to maintain an internal
temperature not to exceed 55
°C. Refer to table 2.1 for drive air watts loss.
Storage Temperature (Ambient)
-40
°C to 65°C (−40°F to 149°F)
Humidity
5% to 95% (non-condensing)
Table A.3 – Terminal Strip Input Specifications
Signal Type
Terminal(s)
Specification
Speed Reference Input
12-15
10 V (@ 50 K ohm input
impedance or 20 mA)
Digital Inputs (1 - 8)
16
+24 VDC Isolated Supply
17
Remote/Local (Default)
18
Ramp1/Ramp2 (Default)
19
Forward/Reverse
(Default)
20
Function Loss
21
Run/Jog
22
Reset
23
Stop
24
Start
Table A.4 – Terminal Strip Output Specifications
Signal Type
Terminal(s)
Specification
Analog Output
10 -11
scaled signal
0-10 VDC or 4-20 mA
No Connection
26
There is no connection to
terminal 26.
Common
27
+24 VDC common