Appendix b - cooling system specifications, Ppendix, Cooling system specifications – Rockwell Automation Liqui-Flo AC Power Modules User Manual
Page 95

Cooling System Specifications
B-1
A
PPENDIX
B
Cooling System Specifications
M/N 41L4060 M/N 41LR4060
M/N 50LW4060
M/N 64LW4060
M/N 50LR4060
M/N 64LR4060
M/N 120L4060
Coolant Type
Potable water
with no
additives.
Refrigerant
Potable water
with no
additives.
Refrigerant
Potable water
with approved
corrosion
inhibitor
1
.
1
Approved corrosion inhibitor: Chemtool, Inc., Crystal Lake, IL., part number CT787-C. Concentration is 2% by volume.
Inlet Coolant
Temperature Range
15
o
C to 40
o
C
(60
o
F to
104
o
F)
2
2
Coolant temperature should be greater than the dew point of the surrounding air to prevent condensation on the tubing and heatsink.
See note
3
.
3
Contact Reliance Electric for coolant circuit requirements.
15
o
C to 40
o
C
(60
o
F to
104
o
F)
2
See note
3
.
15
o
C to 40
o
C
(60
o
F to 104
o
F)
2
Minimum Coolant Flow
Rate at Full Load
7.0 gpm
See note
3
.
5.0 gpm
See note
3
.
8.0 gpm
Differential Coolant
Pressure at Minimum
Flow Rate
3.0 psi
See note
3
.
34.0 psi
See note
3
.
5.0 psi
Maximum Inlet
Pressure
450 psi
See note
3
.
300 psi
See note
3
.
50 psi
Maximum Heat Load
16,000
BTU/hour
16,000
BTU/Hour
25,000
BTU/hour
25,000
BTU/Hour
40,000