Step 8: Verifying the
Installation
Task
Description
Disconnect connector (J3 on PMA board for LiquiFlo 1.0 drives or J4 on PMC board for
LiquiFlo 1.5 drives)
Confirm continuity between the points specified in either
Table A
or
Table B
Reconnect connector (J3 on PMA board for LiquiFlo 1.0 drives or J4 on PMC board for
LiquiFlo 1.5 drives)
A
B
C
J3
Pin 1
Continuity Checks on LiquiFlo 1.0 Drives (M/N’s 50LXXX, 64LXXXX)
Table A J3 Continuity Tests
Test Points
(1)
(1)
If you are unfamiliar with continuity tests, refer to
Performing Continuity
Tests on page 11
.
Meter Reading
J3 End of Cable
Resistor Assembly
End of Cable
(2)
(2)
See
Wiring Diagram for Reference on page 13
.
J3:Pin 1
BUS (+)
Continuity or
approximately zero ohms
J3:Pin 3
BUS MID
J3:Pin 5
BUS (-)
A
B
C
Pin 1
J4
Continuity Checks on LiquiFlo 1.5 Drives (M/N’s LF150XXXX)
Table B J4 Continuity Tests
Test Points
(1)
(1)
If you are unfamiliar with continuity tests, refer to
Performing Continuity
Tests on page 11
.
Meter Reading
J4 End of Cable
Resistor Assembly
End of Cable
(2)
(2)
See
Wiring Diagram for Reference on page 13
.
J4:Pin 1
BUS (+)
Continuity or
approximately zero ohms
J4:Pin 3
BUS MID
J4:Pin 5
BUS (-)
A
B
C