Instruction Manual D2-3536

Step 8: Verifying the
Installation

Task

Description
Disconnect connector (J3 on PMA board for LiquiFlo 1.0 drives or J4 on PMC board for
LiquiFlo 1.5 drives)
Confirm continuity between the points specified in either

Table A

or

Table B

Reconnect connector (J3 on PMA board for LiquiFlo 1.0 drives or J4 on PMC board for
LiquiFlo 1.5 drives)

A

B

C

J3

Pin 1

Continuity Checks on LiquiFlo 1.0 Drives (M/N’s 50LXXX, 64LXXXX)

Table A J3 Continuity Tests

Test Points

(1)

(1)

If you are unfamiliar with continuity tests, refer to

Performing Continuity

Tests on page 11

.

Meter Reading

J3 End of Cable

Resistor Assembly
End of Cable

(2)

(2)

See

Wiring Diagram for Reference on page 13

.

J3:Pin 1

BUS (+)

Continuity or
approximately zero ohms

J3:Pin 3

BUS MID

J3:Pin 5

BUS (-)

A

B

C

Pin 1

J4

Continuity Checks on LiquiFlo 1.5 Drives (M/N’s LF150XXXX)

Table B J4 Continuity Tests

Test Points

(1)

(1)

If you are unfamiliar with continuity tests, refer to

Performing Continuity

Tests on page 11

.

Meter Reading

J4 End of Cable

Resistor Assembly
End of Cable

(2)

(2)

See

Wiring Diagram for Reference on page 13

.

J4:Pin 1

BUS (+)

Continuity or
approximately zero ohms

J4:Pin 3

BUS MID

J4:Pin 5

BUS (-)

A

B

C