Specifications – Rockwell Automation 1440-RMA00-04RC XM-440 Master Relay Module User Manual

Page 10

Advertising
background image

10

Rockwell Automation Publication ENMON-IN440I-EN-P - February 2014

XM-440 Master Relay Module

Specifications

The following table lists the technical specifications for the XM-440 module.

Attribute XM-440

Temperature, operating
IEC 60068-2-1 (Test Ad, Operating Cold),
IEC 60068-2-2 (Test Bd, Operating Dry Heat),
IEC 60068-2-14 (Test Nb, Operating Thermal Shock)

-20…65 °C (-4…149 °F)

Temperature, surrounding air, max

65 °C (149 °F)

Temperature, nonoperating
IEC 60068-2-1 (Test Ab, Unpackaged Nonoperating Cold),
IEC 60068-2-2 (Test Bb, Unpackaged Nonoperating Dry Heat),
IEC 60068-2-14 (Test Na, Unpackaged Nonoperating Thermal Shock)

-40…85 °C (-40…185 °F)

Relative humidity
IEC 60068-2-30 (Test Db, Unpackaged Damp Heat)

5…95% noncondensing

Vibration
IEC 60068-2-6 (Test Fc, Operating)

2 g @ 10…500 Hz

Shock, operating
IEC 60068-2-27 (Test Ea, Unpackaged Shock)

15 g

Shock, nonoperating
IEC 60068-2-27 (Test Ea, Unpackaged Shock)

20 g

Emissions
CISPR 11 (IEC 61000-6-4)

Class A

ESD immunity
IEC 61000-4-2

4 kV contact discharges
8 kV air discharges

Radiated RF immunity
IEC 61000-4-3

10V/m with 1 kHz sine-wave 80% AM from 80…2000 MHz
10V/m with 200 Hz 50% Pulse 100% AM at 900 MHz
10V/m with 200 Hz 50% Pulse 100% AM at 1890 MHz
3V/m with 1 kHz sine-wave 80% AM from 2000…2700 MHz

EFT/B immunity
IEC 61000-4-4

±2 kV at 5 kHz on power ports
±1 kV at 5 kHz on relay and shielded signal ports
±1 kV at 5 kHz on XMbus port

Surge Transient immunity
IEC 61000-4-5

±1 kV line-earth(CM) on relay ports
±2 kV line-earth(CM) on shielded signal ports
±2 kV line-earth(CM) on XMbus port

Conducted RF immunity
IEC 61000-4-6

10V rms with 1 kHz sine-wave 80% AM from 150 kHz…80 MHz

Enclosure type rating

None (open-style)

Voltages/ranges

Supply:
24V DC, 0.2A max, Class 2/SELV

Relay:
250V AC, 50/60 Hz, 3 A resisitive

Power dissipation

3.4 W max

External over-current protection

440-5AFUSEKIT for SELV/PELV power sources

Isolation voltage

250V (continuous), Basic Insulation Type, relay to relay and to all other circuits
Type tested at 1500V AC for 60 s

Advertising