Rockwell Automation Publication ENMON-IN440I-EN-P - February 2014

XM-440 Master Relay Module

Self-Test

The XM-440 module performs a self-test at powerup. The self-test includes a status indicator test and a device test. During
the status indicator test, the indicators are turned on independently and in sequence for approximately 0.25 seconds.

The device test occurs after the status indicator test. The Module Status (MS) indicator is used to indicate the status of the
device self-test.

Reset Switch

The XM-440 module has an external reset switch on top of the module. The Reset switch can be used to reset all latched
relays, including the relays in the Relay Expansion module when it is attached to the XM-440 module.

MS Indicator State

Description

Flashing red and green

Device self-test is in progress.

Solid green or flashing green

Device self-test completed successfully, and the firmware is valid and running.

Flashing red

Device self-test completed, the hardware is OK, but the firmware is invalid. Or, the firmware download is in progress.

Solid red

Unrecoverable fault, hardware failure, or Boot Loader program corruption.

WARNING: When you press the reset button while power is on, an electrical arc can occur. This could cause an explosion in
hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.

IMPORTANT

The Reset switch resets the relays only if the input is no longer in alarm or the condition that caused the alarm is no longer
present.

MASTER RELAY

1440-RMA00-04RC

Reset Switch