1.3. Host Interface Unit (HIU)

The HIU is the point of access to the Inter-Module Bus (IMB) for the module. It also provides power
distribution and local programmable processing power. The HIU is the only section of the I/O module
to directly connect to the IMB backplane. The HIU is common to most Trusted

TM

I/O module types and

has type dependent and product range common functions. Each HIU contains three independent
slices, referred to as A, B, and C.

All interconnections between the three slices incorporate isolation to prevent any fault interaction
between the slices. Each slice is considered a Fault Containment Region (FCR), as a fault on one
slice has no effect on the operation of the other slices.

The HIU provides the following services common to the modules in the family:

1.4. Front Panel Unit (FPU)

The Front Panel Unit (FPU) comprises a Front Panel Interface Unit (FPIU) and a Front Panel Display
Unit (FPDU). The overall FPU contains the necessary connectors, switches, logic, and LED indicators
for the front panel. For every type of Trusted

TM

I/O module, the FPU contains the Slice Healthy,

Active/Standby and Educated indicators (LEDs), and the module removal switches. Additional bicolour
LEDs provide status indication for the individual I/O signals. Serial data interfaces connect the FPU to
each of the HIU slices to control the LED status indicators and monitor the module removal switches.

• High Speed Fault Tolerant Communications with the TMR Processor via the IMB interface.
• FCR Interconnect Bus between slices to vote coming IMB data and distribute outgoing I/O

module data to the IMB.

• Optically isolated serial data interface to the FIU slices.
• Redundant power sharing of dual 24V dc chassis supply voltage and power regulation for

logic power to HIU circuitry.

• Magnetically Isolated power to the FIU slices.
• Serial data interface to the FPU for module status LEDs.
• SmartSlot link between active and standby modules for co-ordination during module

replacement.

• Digital Signal Processing to perform local data reduction and self-diagnostics.
• Local memory resources for storing module operation, configuration, and field I/O data.
• On-board housekeeping, which monitors reference voltages, current consumption and

board temperature.