Trusted, Module t8433 – Rockwell Automation T8433 Trusted TMR Isolated 4-20 mA Analogue Input Module - 20 Channel User Manual

Page 32

Advertising
background image

Trusted

TM

Module T8433

Issue 11 Apr 10

PD-T8433

32

Under normal conditions, an active/standby changeover will only occur if the new active module is
fault-free. Under some circumstances, it is desirable to be able to force a changeover to a known
faulted module. This can be accomplished by opening the Module Removal switches on the currently
active module and pressing the push-button reset on the TMR Processor. This will force the
changeover to proceed even if the new active module is not fault free.