Rack 2: state, Table 6 rack 2: state descriptions, Table 7 rack 2: state bit descriptions – Rockwell Automation T8433 Trusted TMR Isolated 4-20 mA Analogue Input Module - 20 Channel User Manual

Page 19: Trusted, Module t8433

Advertising
background image

Trusted

TM

Module T8433

Issue 11 Apr 10

PD-T8433

19

3.2.2. Rack 2: STATE

This board provides the majority voted numerical input state. This indicates within which threshold
band the field input is in and module channel fault status.

Channel Description

1

Field input channel 1 state

2

Field input channel 2 state

20

Field input channel 20 state

21

Field input channel 1 redundant state

40

Field input channel 20 redundant state

Table 6 Rack 2: STATE descriptions

The numerical input state is returned as an integer value; with the least significant 4-bits indicating the
state. The most significant of these 4-bits indicates the channel fault condition; 1 indicating that a fault
has been detected within the internal operation for that channel.

The least significant 3-bits indicate the threshold band within which the input lies.

Value

Description

7

Unknown

6

Over-range

5

High-High

4

High

3

Normal

2

Low

1

Low-Low

0

Underrange

Table 7 Rack 2: STATE bit descriptions

The input channel has a value 7 (Unknown) when:

1. The input channel cannot be correctly measured by two or more slices of the TMR input

module.

2. The TMR Processor detects a 2-oo-3 channel discrepancy between the three slices of the

TMR input module.

3. The module is simulated (not installed or the TMR Processor cannot communicate with 2-oo-

3 slices of the module).

Advertising