1.2. System Configuration

Figure 3 Backplane Front View

The backplane contains a user-configurable setting for system identification. In the Trusted

TM

Expander Chassis, this setting represents the system number 0 to 15. The setting is implemented via
three 4-position DIP switches (IDA, IDB and IDC) and is provided to the Trusted

TM

TMR Processor

connector. Adjacent to the three DIP switches is a table which shows the required settings for each
system. See Tables 1 and 2 below.

Note: On some early models of Trusted

TM

Expander Chassis, the designation of the ‘Off’ and ‘On’

switches detailed in the table on the backplane was reversed.

In all cases, ‘1’ = Off and ‘0’ = On and ‘down’ means logic 1.

All three address settings must be the same, otherwise an error condition will be reported.

The first expander chassis should be set to IDA=2, IDB=2 and IDC=2, the second expander chassis
should be set to IDA=3, IDB=3 and IDC=3. The last expander chassis should be set to IDA=8, IDB=8
and IDC=8.

System

ID A.B.C

ID

1

2

3

4

0

0

0

0

0

1

0

0

0

1

2

0

0

1

0

3

0

0

1

1

4

0

1

0

0

5

0

1

0

1

6

0

1

1

0

7

0

1

1

1

8

1

0

0

0

9

1

0

0

1

10

1

0

1

0

11

1

0

1

1

12

1

1

0

0

13

1

1

0

1

14

1

1

1

0

15

1

1

1

1

1 - OFF

0 - ON

Table 1 System ID Settings