Maintenance, Safety considerations, Specifications – Rockwell Automation T3441A ICS Regent DC Digital Output Module 24 VDC User Manual
Page 12
 
DC Digital Output Module (T3441A)
 
1 2  
Industrial Control Services
control logic by using a contact element (or similar element) 
with the output point name. 
Maintenance
No periodic maintenance or calibration is required for this 
module. 
Fuses for each output are located within the module. To 
replace a blown fuse the output module must be removed from 
the I/O chassis and opened. To open the output module, 
remove four screws from the side of the module’s clamshell. 
Remove the blown fuse from its retaining clips (on the circuit 
board) and replace it. 
To prevent damage to the module, replacement fuses must be 
of the same rating and type (see Specifications, below). 
To prevent electrostatic damage to sensitive module circuits, 
maintenance personnel should always use the proper anti-
static work areas and grounding straps when handling or 
working with circuit boards. 
Safety Considerations
The DC digital output module is TÜV certified as non-
interfering, and can be used in a safety system for simplex 
non-safety critical outputs. For safety critical outputs, 
guarded output modules should be used (model T3461A, 
T3481 or T3485 are recommended). 
Specifications
Safetybus Power
0.8 load units
Number of Outputs
16 circuits divided into two 
groups of 8 circuits each 
Voltage Range
18 to 30 VDC
Load Current
2 amps maximum per output 
0
°
to 60
°
C