Rockwell Automation T3441A ICS Regent DC Digital Output Module 24 VDC User Manual
Page 13
 
(T3441A) DC Digital Output Module
 
P D - 6 0 1 5 M a r - 0 6  
13
Minimum Load
0 mA
On State Drop
0.5 volts maximum @ 2 amps
Surge Current
15 amps, 20 msec
Output Leakage
1 mA maximum
Fusing
One 3 A, 250 V, fast-acting 
(3AG) per output, located 
inside module 
Turn-On Delay
1.0 msec, maximum
Turn-Off Delay
1.0 msec, maximum
Heat Dissipation
16 Watts, 54 BTUs/hour
Over voltage Protection
45 VDC, continuous
Isolation
2500 volts minimum (field 
wiring to control logic) 
2500 volts minimum (output 
group 1-8 to output group 9-
16) 
Operating Temperature
0
°
to 60
°
C
(32
°
to 140
°
F)
Storage Temperature
-40
°
to 85
°
C
(-40
°
to 185
°
F)
Operating Humidity
0 to 95% relative humidity, 
non-condensing 
Vibration
10 to 55 Hz:
 
±0.15mm 
Shock
Operating:
 
15 g, ½ sine wave, 11 msec 
Electromagnetic 
Interference 
•
IEC 801 Part 2 - Electrostatic
Discharges
•
IEC 801 Part 3 - Radiated
Electromagnetic Fields
 
Level 3: Contact discharge of 
6 kV 
Level 3: 10 V/M, 27 MHz - 
500 MHz