DC Digital Output Module (T3441A)
 
4  
Industrial Control Services
Active and Fault Status Indicators
These green and red LEDs indicate the overall health of the 
module. During normal operation, the green ACTIVE 
indicator flashes at the controller’s scan rate. If a module 
fault is detected the red FAULT indicator turns on and the 
green ACTIVE indicator turns off. 
Shutdown Indicator
Upon loss of communications with the controller, output 
modules enter either a shutdown or hold fault mode. If the I/O 
unit is set to shutdown, the red SHUTDOWN
indicator will
turn on when communications with the controller are lost. If 
the I/O unit is set to hold, the SHUTDOWN indicator will 
always be off (see page 8, Fault Mode Jumper). 
When the module is installed in the I/O chassis or when logic 
power (from the I/O power supply modules) is first applied to 
the module, it will be in the shutdown mode until the first 
output scan, regardless of the fault mode jumper settings. 
Also, removing two I/O transceiver modules, two I/O power 
supply modules, or two power legs will cause the module to be 
in the shutdown mode. 
Output Status Indicators
The output status indicators are yellow LEDs, located on the 
field side of the output. There are 16 output status indicators, 
— one for each output. These indicators are lit when the 
output FET is energized to turn on the load. 
Blown Fuse Indicators
The red BLOWN FUSE indicators turn on when one of the 
fuses in the corresponding output group opens. A blown fuse 
will also cause the module’s FAULT indicator to turn on. 
Field power must be connected to the module for it to detect a 
blown fuse. Refer to Maintenance, page 12, for fuse 
replacement instructions. 